
Add to Cart
1.LCD display, blue backlight, suitable for dark places
2.Automatic Shutdown
3.Press HOLD key to keep data
Technical Specification
1.Base Conditions and Working Conditions
Influence Quantity |
Base Condition |
Working Conditions |
Remark |
Ambient Temp |
23°C±1°C |
-10°C~40°C |
|
Ambient Humidity |
40%~60% |
<80% |
|
Signal Waveform |
sine wave |
sine wave |
β=0.05 |
Signal Frequency |
50HZ±1HZ |
45HZ~65HZ |
|
Meter Working Volt |
9V±0.1V |
9V±1V |
|
External Electric, Magnetic Field |
To be avoided |
||
Measured Wire Position |
Measured wire at approximately the geometric center of the clamp |
2.General Specification
Function |
Phase, AC current, AC voltage, AC leakage current, direct test of phase sequence; transformer groups, inductive, capacitive circuit discrimination; indirect test of power factor and power |
Power |
DC9V alkaline batteries(1.5V AA×6) |
Consumption |
About 35mA at most with enabled backlight, battery working continuously for about 40 hours |
-3- About 5mA with disabled backlight, battery working continuously for about 300 hours |
|
Display Mode |
LCD display, blue backlight, suitable for dark places |
LCD Size |
70mm×62mm |
LCD Display Field |
64mm×54mm |
Meter Size |
Length, Width, Height:196mm×92mm×54mm |
Clamp Size |
φ7.5mm×13mm |
Sampling Rate |
About 3 times/second |
Measurement Range |
AC Voltage:0~20V/200V/500V |
AC Current:0~200mA/2A/10A |
|
Phase:0~360° |
|
Measured Signal Amplitude in Phase Test |
U1-U2 phase test:30V~500V |
I1-I2 phase test:10mA~10.00A |
|
U1-I2 or I1-U2 phase test:10V~500V, 10mA~10.00A |
|
Data Hold |
Press HOLD key to keep data, "DH" symbol appears |
Automatic Shutdown |
Automatic shutdown about 15 minutes later after launching to reduce battery consumption |
Voltage Detection |
Low battery symbol “ " appears to remind the replacement of battery when the battery voltage drops below 7.8V~8V. |
Weight |
Main Unit about 550g(with battery), clamp about 170g×2, test line about 250g |
Test Line Length |
1.5m |
Current Clamp Length |
2m |
Working Temperature and Humidity |
-10°C~40°C;below 80%Rh |
Storage Temperature and Humidity |
-10°C~60°C; below 70%Rh |
Input Impedance |
Input impedance for all test voltage range:2MΩ |
Input impedance when testing U1U2 phase:40KΩ |
|
Withstand Voltage |
Withstand 1000V/50Hz sine wave AC voltage for 1 minute between the meter lines and shell; Withstand 500V/50Hz AC voltage sine wave for 1 minute between the two voltage inputs |
Insulation |
≥10MΩ between meter lines and shell or between the two voltage inputs |
Structure |
-4- Double insulation |
3.Intrinsic error and performance indicators under base conditions
Category |
Measurement Range |
Resolution |
Intrinsic Error |
Voltage |
20V |
0.01V |
±(1.2%rdg+2dgt) |
200V |
0.1V |
||
500V |
1V |
||
Current |
200mA |
0.1mA |
±(1.0%rdg+2dgt) |
2A |
1mA |
||
10A |
10mA |
||
Phase |
0~360° |
1° |
±3° |